Difference Between Busbar Protection (BB) and Local Breaker Backup (LBB) Protection

While both BB (Busbar Protection) and LBB (Local Breaker Backup) involve tripping multiple breakers, their purpose, activation conditions, and affected zones are different. Here’s a clear comparison:


Key Difference Table

FeatureBB Protection (Busbar Protection)LBB Protection (Local Breaker Backup)
PurposeDetects faults within the busbar zone and trips all connected breakers to isolate the faulty bus section.Provides backup protection when a breaker fails to operate during a fault.
Trigger ConditionDetects a differential current imbalance in the bus zone using relays like 87B.Detects breaker failure by checking if the breaker remains closed despite receiving a trip command.
Fault LocationInside the busbar zone (e.g., bus insulator flashover, conductor contact).Outside the busbar zone (e.g., line fault or transformer fault when the breaker fails to trip).
ActionTrips all breakers connected to the faulty bus section.Trips only the upstream and downstream breakers to isolate the faulty section.
Protection Scheme RolePrimary Protection for busbar faults.Backup Protection for failed breaker conditions.
SpeedOperates very fast (within milliseconds) to minimize system disruption.Operates with a slight time delay to allow the primary breaker time to operate first.
Relay Codes UsedRelays like 87B for busbar differential protection.Relays like 96 LBB for breaker failure backup protection.

Example Scenario 1: Busbar Protection (BB Function)

➡️ Fault Location: Inside the 220kV busbar
➡️ The 87B relay detects a differential current imbalance.
➡️ The 96 BB relay trips all breakers connected to the busbar to isolate the faulty bus section.

✅ Ensures the entire faulty bus section is isolated instantly.


Example Scenario 2: Local Breaker Backup (LBB Function)

➡️ Fault Location: On Line 1 connected to the 132kV breaker.
➡️ The primary relay (e.g., 21 Distance Relay) sends a trip signal to Breaker A.
➡️ Breaker A fails to open.
➡️ The LBB relay detects this failure and trips:
✅ The upstream incomer breaker to cut power supply.
✅ The adjacent feeder breaker to isolate the faulted line.

✅ Ensures the system remains stable even if a breaker fails.


Key Difference in Control Area:

  • BB Protection → Protects the entire busbar zone.
  • LBB Protection → Acts on a single breaker’s failure to isolate the fault using surrounding breakers.

Quick Summary Analogy:

  • BB Protection = Fire Alarm → Detects a fire in the building and activates all sprinklers to control it.
  • LBB Protection = Fire Exit Plan → If the primary fire exit is blocked (breaker failure), it directs people to alternative exits (upstream/downstream breakers) to ensure safety.
Scroll to Top